WorcesterAutomation - Communication -
Control and Evaluation of System Status

ACCESS system

BenefitsFeaturesSpecificationsMonitoring LEDs

 Back to home page


The Access System is a totally integrated actuation package to include actuator, solenoid, limit switches & monitoring LEDS in as a single unit.

The Access system with the clear Lexan cover gives a clear view of the 4 colored LEDS

 

The Access system with the Cast Aluminum Impregnated and Anodized cover for complete NEMA ratings.

 

 

The Access System is built around the rugged construction of Worcester Series 39 Pneumatic Actuator. Stainless Steel Guide Rods make the series 39 actuator unique. It is the only double piston rack and pinion actuator designed with piston guide rods.

Back to Top Back to home page

LEDs Show Position & Status

Valve position can be monitored via limit switches or visually through the optionally available Lexan end cover. Leds assist during valve setup, calibration & trouble shooting.

Coil continuity and voltage are verified by the orange & yellow leds.

Open and closed are monitored by the Green & Red leds.

 

Limit switches are easily adjusted with the assistance of the leds.

Back to TopBack to home page

Features:

Back to TopBack to home page

Benefits:

Back to TopBack to home page

Specifications

Limit Switches
SPDT 15A, 125, 250VAC.5A, 125DC .25A, 250DC
DPDT 10A, 125 250VAC.3A, 125DC .15A, 250DC
AC Proximity Switch: 200ma max. continuous. Derated by (-3) ma/Dec at 50-85degC
20-260AC, 45-65HZ
DC Proximity Switch: 200ma max. 9.6-55VDC
Gold Contacts: 1A, 125VAC1A, RES (.5A ID) 28VDC
 
Solenoid:
3 watts, 12,24VDC24,120,240VACCV .03CV with Spool .55
Cycle time of actuator:
Sizes 10 & 15 with spool valve is 1sec or less.
Sizes 10 & 15 without spool valve is approximately 2sec & 4sec respectively
 
Terminal Strip:
8 points, 12AGW
 
Conduit
3/4" NPT Female
 
Ambient Temperature
150degF maximum
 
Enclosure
Standard with metal cover: Watertight, Corrosion resistance, NEMA 4, 4X, 7,9,12,
Cast Aluminum impregnated and anodized, Class 1 Div. 1 & 2, Group A,B,C,D
Class ll Div. 1 & 2, Group E.F.G Class lll Div. 1 & 2
 
Clear Cover: Lexan type 4 & 4X